Interpretation IC 15-1994-7 - August 1999

Print This Email This

ANSI/ASHRAE Standard 15-1994, Safety Code For Mechanical Refrigeration

Request from: David M Elovitz, Energy Economics, Inc. 26 Robinhood Road, Natick, MA 01760.

References. This request refers to Standard 15-1994, Subclauses 8.13.2 through 8.13.5

Background. Subclause 8.13.2 requires a refrigerant detector which will activate an alarm and mechanical ventilation in accordance with 8.13.4 at flow rates prescribed in 8.13.5, at a value not greater than the corresponding TLV-TWA (or toxicity measure consistent therewith).

Question. Is it the intent of 8.13.2 through 8.13.5 that the mechanical ventilation system have a source of emergency electric power available.

Answer. No